无码视频在线,东京热一区二区三区无码,精品热线九九精品视频,精品国产综合成人亚洲区2022,国产精品久久久久蜜芽,亚洲va国产日韩欧美精品,台湾亚洲自偷自拍另类12p

News
Your location:Home > News > Company News

Matters needing attention in field application of small current grounding line selection device

AddTime:2020-09-17 13:36:58   Views:     【 Big Mid Small 】   Print   Close

In order to determine the fault line, the traditional method is to pull the gate one by one, so as to select the fault line and judge the fault location. This method consumes time and reduces the reliability of power supply. Moreover, many times of closing and opening will have impact on the power system and main transformer, and using the switch repeatedly will reduce its service life. In order to solve this problem in time, the small current grounding line selection device is installed.

There are also a lot of matters needing attention in the field installation and use of the small current grounding line selection device. If you do not pay attention to it, it may lead to disaster. As a standardized configuration, the selection of equipment should be determined according to the actual situation on site, and the small current grounding system should be treated strictly.

The characteristics of zero sequence current transformer on the same site are basically the same, so the zero sequence current transformer matching with the company should be selected.

The polarity of all zero sequence current transformers must be strictly consistent, especially the site where zero sequence current transformer and three-phase current transformer are mixed. For systems with more than two busbars, the polarity of current transformers of all incoming devices must be consistent.

The zero sequence current transformer is generally installed under the cable head: the cable sheath grounding wire above the zero sequence transformer must be grounded at the line side after passing through the current transformer; the cable skin grounding under the zero sequence transformer cannot pass through the zero sequence transformer to avoid the formation of short circuit loop.

A large current transformer must be installed as an outgoing lead-in device for the line with double or multi cable power supply.

For all systems with cable outgoing lines, a zero sequence transformer and a secondary line grounding device are installed on each outgoing line. The polarity of current transformer must be consistent.

Under the condition of ensuring the normal operation of the device, the system simulation grounding debugging must be done. In the next article, the small editor will explain the analog grounding debugging method of small current grounding line selection device.


Prev:Preparation before installation of power quality online monitoring device  Next:Application of arc light protection system for switchgear
Back To Top
Copyright ? Bao Ding Shi Simaier Electric Co., Ltd. All Rights Reserved  
  • <strike id="0eits"></strike>
    <track id="0eits"><strike id="0eits"><thead id="0eits"></thead></strike></track>
      <i id="0eits"></i>
    • <i id="0eits"><legend id="0eits"></legend></i>
        1. <abbr id="0eits"></abbr>

        无码视频在线,东京热一区二区三区无码,精品热线九九精品视频,精品国产综合成人亚洲区2022,国产精品久久久久蜜芽,亚洲va国产日韩欧美精品,台湾亚洲自偷自拍另类12p 免费看无码大黄网站 亚洲中文无码亚洲人成频 午夜尤物禁止18点击进入 久久黄色视频导航 欧美精品九九99久久在观看